Technical data

Relative Humidity
0...100 % RH
Temperature
-25 ... +125 °C
Signal output
0...10 V
0...20 mA (Humidity)
4...20 mA
Supply voltage
3/4-wire 15 ... 30 V DC /24 V AC
2-wire 12 ... 30 V DC
2-wire 12 ... 30 V DC

KC - duct mounted

Heavy-duty transmitters with analogue output for advanced requirements

Features

  • Operating temp. up to 125 °C
  • Accuracy H. ±2% RH (5…95 % at 10…40 °C)
  • Accuracy T. ± 0,2 K with voltage output
  • Accuracy T ± 0,3 K with current output
  • Current outputs galvanically isolated
  • Stainless steel sensor tube
  • IP65

Heavy-duty transmitters to measure humidity and temperature with advanced requirements. The KC transmitters are supplied with a robust, pressure die-cast aluminium housing and a stainless steel tube. They can measure relative humidity and temperature, in air and other non-aggressive gases, for operating temperatures up to 125 °C. These sensors are ideally suited to industrial applications, e.g. drying processes.

Capacitive MELA® sensorchips
Equipped with the highly dynamic capacitive MELA® sensor element, the sensor provides reliable performance across the full humidity range. Using the MELA® sensor element ensures long-term stability, resistance to dew formation, minimal hysteresis, and strong dynamic capabilities.

Often used in

  • Agriculture & food industry
  • Chemical industry
  • Clean rooms
  • Climate chambers
  • Drying of tea, corn, meat
  • Drying plants
  • Paper & print
  • Pharmaceutical industry
  • Process and factory automation